Measurement and control
The measurement of actual values is extremely important for the efficient operation of ventilation systems. For this task, HLU has special components that can be used in chemically aggressive exhaust air.
The measured values are used for simple system monitoring or as input signals for a higher-level control system that controls the actuators in the system in question.
Variable volume flow controller with auxiliary power
HF – VRR
Application
- used to keep air flows constant under changing pressure conditions
- full shut-off possible due to integrated tight-closing shut-off damper
Features
- volume flow from 50 to 4500 m³/h
- minimum pressure difference 100 Pa at nominal volume flow
- available in 12 nominal diameters from 110 to 400 mm connection diameter
Volume flow | 50 to 4.500 m³/h |
---|---|
Pressure difference | minimum pressure difference 100 Pa at nominal volume flow |
Nominal diameters | 12 nominal diameters from 110 to 400 mm |
Material | PPs, PVC, PP, PE |
Connection options | flange or sleeve connection |
Advantages:
- fast, precise regulation with an accuracy of +/- 5% of the set volume flow.
- tight closing in accordance with DIN 1946-4 | airtight shut-off
- possibility of using controllers from different manufacturers either electrically or pneumatically
- differential pressure determined by means of integrated Venturi nozzle
Volumetric flow regulator without auxiliary power
HF – VRM
Application
- used to keep air flows constant under changing pressure conditions
Features
- volume flow from 75 to 3200 m³/h
- minimum pressure difference 100 Pa at nominal volume flow
- available in the nominal diameters from 110 to 315 mm connection diameter
Volume flow | 75 to 3.200 m³/h |
---|---|
Pressure difference | minimum pressure difference 100 Pa at nominal volume flow |
Nominal diameters | von 110 – 315 mm |
Material | PPs, PVC | Special materials optionally available |
Connection options | flange or sleeve connection |
Advantages:
- regulation without the need for auxiliary energy
- adjuster with scale
Volumetric flow regulator
VFL
Application
- Constant volume flow controller in round design for constant control of airflows
Features
- volume flow from 14 to 764 m³/h
- available in the nominal diameters from 90 to 250 mm connection diameter
Volumetric flow monitoring
HF – VRR measuring nozzle
Application
- used to measure air flows
Features
- volume flow from 50 to 4500 m³/h
- available in the nominal diameters from 110 to 400 mm connection diameter
Volume flow | 50 to 4.500 m³/h |
---|---|
Nominal diameters | from 110 to 400 mm |
Material | PPs, PVC | Special materials optionally available |
Connection options | flange or sleeve connection |
Advantages:
- differential pressure determined by means of integrated venturi nozzle
Airstream monitoring
HF – ASM-MU
Application
- used to monitor airflows
Features
- available in the nominal diameters from 75 to 400 mm connection diameter
Nominal diameters | from 75 to 400 mm |
---|---|
Material | PPs, PVC | Special materials optionally available |
Design | integrated evaluation electronics, output relays, adjustment potentiometers and LEDs, and a time relay for start-up suppression |
Connection options | flange or sleeve connection |
Advantages:
- calorimetric sensor in protective plastic housing