Roof fans made of plastic by HLU
HF D 15/17, HF D 16 and HF D 13

Roof Fans Made of Plastic – Chemically Resistant and Ideal for Outdoor Use
HLU roof fans are made of chemically resistant plastic and are specifically designed for vertical suction and outdoor installation.
They are corrosion-resistant, weatherproof, and available in ATEX-certified versions for Zone 1 and Zone 2.
Advantages
- Corrosion-resistant plastics - durable against aggressive media
- Weatherproof design | Safe drainage of rainwater - ideal for outdoor use
- Compact construction is optimal for confined installation situations
- Easy flange mounting enables quick and safe installation
- Various versions for different performance ranges and installation situations
- Comprehensive accessories provide flexible adaptation options for various requirements
Application
- Reliable extraction of corrosive gases and contaminated air streams
- Safe handling of air in potentially explosive environments (Ex Zone 1 and Ex Zone 2)
Design
- Internal motors separated from the airflow are protected from aggressive media
- No metal parts in the airflow
- Motor options: Use of explosion-proof motors (Ex-motors) or energy-efficient EC motors
- ATEX option: Explosion-proof motors for Zone 1 and Zone 2
- Standard equipment: Equipped with a repair switch or explosion-proof terminal box for safe and convenient maintenance
- Versatile material options: Available in PPs, PPs-el, PVC, and more
Typical Application Areas
The Perfect Exhaust Air Solution for Various Industries
HLU roof fans provide a reliable exhaust air solution for industries where safety and efficiency are top priorities.
They are specifically designed for buildings without a central ventilation system and are used in areas where contaminated exhaust air needs to be safely and reliably extracted.
HF D 15/17 & HF D 16 – For the Highest Demands
Ideal for the medical and hygiene sector, science and research, laboratory facilities, food industry, as well as the chemical and pharmaceutical industry.
The roof fans ensure efficient exhaust air management in laboratories (e.g., fume hoods), schools, and research facilities where the highest air quality is required.
HF D 13 – High Performance for Large Air Volumes
Specifically developed for applications with high exhaust air volumes, the HF D 13 roof fans are the perfect choice for the electroplating industry, composting plants, food industry, and the chemical and pharmaceutical industry.
These roof fans guarantee powerful, safe, and efficient extraction of aggressive gases and large air volumes.
Medical and Hygiene Sector

Food Industry

Science and Research

Electroplating Industry

Laboratory and Research Facilities

Composting

Chemical and Pharmaceutical Industry

Product Overview
Features
HF D 15/17

- Volume flow: 50 - 3,500 m³/h
- Maximum pressure difference: Up to 1,400 Pa
- Available in 6 nominal sizes: Suction diameters from 110 to 315 mm
HF D 16

- Volume flow: 500 - 8,000 m³/h
- Maximum pressure difference: Up to 1,400 Pa
- Available in 3 nominal sizes: Suction diameters from 315 to 400 mm
HF D 13

- Volume flow: 4,000 - 40,000 m³/h
- Maximum pressure difference: Up to 1,000 Pa
- Available in 5 nominal sizes: Suction diameters from 500 to 1000 mm
Tender Text HLU / HF Roof Fans
HF D ...-15 / 17 D
HF - Roof Fan
Corrosion-resistant plastic roof fan with a robust, rotationally sintered housing made of PEs, featuring single-sided suction. Equipped with splinter protection in accordance with accident prevention regulations, starting from size 160, as plastic-coated wire mesh.
When mounted vertically, the exhaust air is discharged vertically according to the requirements for contaminated exhaust air. All components exposed to the exhaust air medium are made of plastic or are plastic-coated.
The impeller features backward-curved blades in an injection-molded design, securely mounted on the motor shaft using a taper-lock bushing. The impeller is statically and dynamically balanced, meeting a balancing quality of at least G 6.3 (DIN ISO 21940-11).
Includes an internal motor encapsulated against the exhaust medium and an externally mounted repair switch for standard motors (without explosion protection) or an externally mounted terminal box for explosion-proof motors. The required external ventilation for the motor is provided through externally routed ducts.
HF D ...-15 / 17 D EC
HF - Roof Fan
Version with EC Motor
Corrosion-resistant plastic roof radial fan with a robust, rotationally sintered housing, featuring single-sided suction. The fan is equipped with splinter protection according to accident prevention regulations, starting from size 160, using plastic-coated wire mesh.
When mounted vertically, the exhaust air is discharged vertically in compliance with the requirements for contaminated exhaust air. All components exposed to the exhaust air medium are made of plastic or are fully encapsulated in plastic.
The impeller features backward-curved blades in an injection-molded design, securely mounted on the motor shaft using a taper-lock bushing. The impeller is statically and dynamically balanced, achieving a balancing quality of at least G 6.3 (DIN ISO 21940-11).
Includes a highly efficient internal EC motor, encapsulated against the exhaust medium, and an externally mounted repair switch. The required external ventilation for the motor is provided through externally routed ducts.
| Manufacturer | : Hürner Luft- und Umwelttechnik | |
| Type | : HF D ...-.. D | |
| Housing Material | : PEs | |
| Impeller Material | : PPs | |
| Inlet Diameter | : ... | mm |
| Installation Position | : ... | |
| Medium | : Exhaust air | |
| Volume Flow | : ... | m³/h |
| Total Pressure Difference | : ... | Pa |
| Static Pressure Difference | : ... | Pa |
| Sound Pressure Level Lp8A (1 m) | : ... | dB(A) |
| SFP | : ... | W/(m³/s) |
| Motor Power | ... | kW |
| Voltage | 400 | V |
| Frequency | 50 | Hz |
| Rated Current | ... | A |
| Enclosure / Motor Protection | IP 55 / Kaltleiter |
| Manufacturer | : Hürner Luft- und Umwelttechnik | |
| Type | : HF D ...-.. D EC | |
| Housing Material | : PEs | |
| Impeller Material | : PPs | |
| Installation Position | : Vertikal | |
| Inlet Diameter | : ... | mm |
| Medium | : Abluft | |
| Volume Flow | : ... | m³/h |
| Total Pressure Difference | : ... | Pa |
| Static Pressure Difference | : ... | Pa |
| Sound Pressure Level Lp8A (1 m) | : ... | dB(A) |
| Motor Power | ... | kW |
| Voltage | 1~ 230 | V |
| Frequency | 50 | Hz |
| Rated Current | ... | A |
| Enclosure / Motor Protection | IP 55 / im Motor integriert |
Tender Text HF D ...-15 / 17 D
Click on ‘Download’ to get the complete tender text as a Word document.
Tender Text HF D ...-15 / 17 D EC
Click on ‘Download’ to get the complete tender text as a Word document.
HF D ...-16 D
HF - Roof Fan
Corrosion-resistant plastic roof fan with a housing made of thermoplastic plastics, featuring a robust, deep-drawn design with single-sided suction. Equipped with splinter protection according to accident prevention regulations (UVV) using plastic-coated wire mesh.
When mounted vertically, the exhaust air is discharged vertically according to the requirements for contaminated exhaust air. All components exposed to the exhaust air medium are made of plastic or are fully plastic-coated. The shaft passage is minimized using a felt ring seal.
The impeller features backward-curved blades, mounted cantilevered on the motor shaft, and is statically and dynamically balanced with a balancing quality of at least G 6.3 (DIN ISO 21940-11).
Includes an internal motor encapsulated against the exhaust medium and an externally mounted repair switch for standard motors (without explosion protection) or an externally mounted terminal box for explosion-proof motors. The required external ventilation for the motor is provided through externally routed ducts.
| Manufacturer | : Hürner Luft- und Umwelttechnik | |
| Type | : HF D ...-16 D | |
| Housing Material | : PEs | |
| Impeller Material | : PPs | |
| Inlet Diameter | : ... | mm |
| Installation Position | : ... | |
| Medium | : Exhaust air | |
| Volume Flow | : ... | m³/h |
| Total Pressure Difference | : ... | Pa |
| Static Pressure Difference | : ... | Pa |
| Sound Pressure Level Lp8A (1 m) | : ... | dB(A) |
| SFP | : ... | W/(m³/s) |
| Motor Power | ... | kW |
| Voltage | 400 | V |
| Frequency | 50 | Hz |
| Rated Current | ... | A |
| Enclosure / Motor Protection | IP 55 / Kaltleiter |
HF D ...-13 D
HF - Roof Fan
Corrosion-resistant plastic roof fan with a housing made of thermoplastic plastics, featuring a robust, welded design with single-sided suction. The fan is equipped with splinter protection according to accident prevention regulations (UVV) using plastic-coated wire mesh.
When mounted vertically, the exhaust air is discharged vertically according to the requirements for contaminated exhaust air. All components exposed to the exhaust air medium are made of plastic or are fully plastic-coated. The shaft passage is minimized using a felt ring seal.
The impeller features backward-curved blades, mounted cantilevered on the motor shaft, and is statically and dynamically balanced with a balancing quality of at least G 6.3 (DIN ISO 21940-11).
Includes an internal motor encapsulated against the exhaust medium and an externally mounted repair switch for standard motors (without explosion protection) or an externally mounted terminal box for explosion-proof motors. The required external ventilation for the motor is provided through externally routed ducts.
| Manufacturer | : Hürner Luft- und Umwelttechnik | |
| Type | : HF D ...-13 D | |
| Housing Material | : PEs | |
| Impeller Material | : PPs | |
| Inlet Diameter | : ... | mm |
| Installation Position | : ... | |
| Medium | : Exhaust air | |
| Volume Flow | : ... | m³/h |
| Total Pressure Difference | : ... | Pa |
| Static Pressure Difference | : ... | Pa |
| Sound Pressure Level Lp8A (1 m) | : ... | dB(A) |
| SFP | : ... | W/(m³/s) |
| Motor Power | ... | kW |
| Voltage | 400 | V |
| Frequency | 50 | Hz |
| Rated Current | ... | A |
| Enclosure / Motor Protection | IP 55 / Kaltleiter |
Tender Text HF D ...-16 D
Click on ‘Download’ to get the complete tender text as a Word document.
Tender Text HF D ...-13 D
Click on ‘Download’ to get the complete tender text as a Word document.
Housing and impeller made of corrosion-resistant plastic

Flame-retardant Polyethylene | PEs
✓ Good resistance to inorganic acids
✓ High UV resistance
✓ Good low-temperature toughness
✓ Affordable price
Standard material for sintered housings

Polyethylene | PE-el
✓ Good resistance to inorganic acids
✓ High UV resistance
✓ Good low-temperature toughness
✓ Affordable price
Standard material for sintered housings

Flame-retardant Polypropylene | PPs
✓ Good resistance to inorganic acids
✓ Good mechanical strength
✓ Affordable price
Standard material for impellers made of thermoplastic

Flame-retardant, electrically conductive Polypropylene | PPs-el
✓ Good resistance to inorganic acids
✓ Suitable for ATEX Zone 1
Roof Fans with EC Motor
Energy-efficient exhaust air handling
HLU Roof Fans with EC Technology: Efficiency Meets Modern Control
HLU roof fans with EC technology combine maximum efficiency with advanced control technology, offering a sustainable exhaust air solution for a wide range of applications.
The latest EC technology significantly reduces power consumption while allowing precise and stepless speed control.
Advantages of EC Technology:
- Energy-efficient: Significantly lower power consumption compared to conventional motors
- High efficiency: Optimized performance with minimal energy use
- Stepless control: Perfect adaptation to individual air requirements
- Easy integration: Plug-and-play solution

Explosion protection according to ATEX 2014/34/EU
HLU Roof Fans – Safe, Efficient, and Certified
The ATEX Directive 2014/34/EU regulates explosion protection for products used in hazardous areas.
Our HLU roof fans in explosion-proof design meet the strict requirements of the ATEX Directive 2014/34/EU and provide maximum safety in Zone 1 and Zone 2.


Thanks to the use of electrically conductive and flame-retardant plastics (PPs-el) and the integration of explosion-proof motors, the fans are specifically designed for handling chemically aggressive and potentially explosive exhaust air in ATEX Zone 1.
ATEX version
Zone 2 inside / no zone outside
- Housing and impeller
made of electrically conductive and flame-retardant PPs-el - Shaft seal
for maximum operational safety and protection against leakage - Optional protective grid
on the suction and outlet sides for protection against foreign bodies - Type label with Ex marking and documentation
for easy identification and compliant use in zone 1 and 2
ATEX version
zone 2 inside / zone 2 outside
- Housing and impeller
made of electrically conductive and flame-retardant PPs-el - Shaft seal
for maximum operational safety and protection against leakage - Optional protective grid
on the suction and outlet sides for protection against foreign bodies - Motor for single-stage network operation
II 2G Ex eb II T3 Gc - Motor for inverter operation
II 2G Ex db eb IIC T4 Gb with PTC - Type label with Ex marking and documentation
for easy identification and compliant use in zone 1 and 2
ATEX version
zone 1 inside / zone 2 outside or
zone 1 inside / zone 1 outside
- Housing and impeller
made of electrically conductive and flame-retardant PPs-el - Shaft seal
for maximum operational safety and protection against leakage - Optional protective grid
on the suction and outlet sides for protection against foreign bodies - Motor for single-stage network operation
II 2G Ex eb II T3 Gc - Motor for inverter operation
II 2G Ex db eb IIC T4 Gb with PTC - Type label with Ex marking and documentation
for easy identification and compliant use in zone 1 and 2
HLU Roof Fans Catalog
HF D 15/17 | HF D 16 | HF D 13
Find more details about our HLU roof fans in our catalog.
Download all technical data, dimensions, and descriptions conveniently as a PDF now.
Download catalog
HF D 15/17 | HF D 16 | HF D 13
Get all technical details, product drawings, and information about additional accessories.

Request now
Do you have any questions or would you like a quote? Contact us directly!
Personal contact for your inquiry
Adrian Costiniuc
Head of International Sales
Fans and ventilation components
Sarah Di Cicco
Head of International Sales - East-Asia
Fans and ventilation components
Christoph Reimers
Head of International Sales - East-Asia
Fans and ventilation components
With four business divisions, HLU offers perfect solutions for all requirements.